5337D 2-wire transmitter with HART protocol

Application

  • Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
  • HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
  • Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
  • Amplification of bipolar mV signals to standard 4...20 mA current signals.
  • Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.

Technical characteristics

  • HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
  • The HART 7 protocol offers:
    • Long Tag numbers of up to 32 characters.
    • Enhanced Burst Mode and Event notification with time stamping.
    • Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
    • Process signal trend measurement with logs and summary data.
    • Automatic event notification with time stamps.
    • Command aggregation for higher communication efficiency.
  • 5337D is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
  • Continuous check of vital stored data.
  • Meeting the NAMUR NE 21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337D meets NAMUR NE43 and NE89 recommendations.

Mounting / installation

  • For DIN form B sensor head mounting.
  • Configuration via standard HART communication interfaces or by PR 5909 Loop Link.

Download Datasheet

Environmental Conditions

Operating temperature

-40°C to +85°C

Calibration temperature

20...28°C

Relative humidity

< 95% RH (non-cond.)

Protection degree (encl./terminal)

IP68 / IP00

Mechanical specifications

Dimensions

Ø 44 x 20.2 mm

Weight approx.

50 g

Wire size

1 x 1.5 mm2 stranded wire

Screw terminal torque

0.4 Nm

Vibration

IEC 60068-2-6

2...25 Hz

±1.6 mm

25...100 Hz

±4 g

Common specifications

Supply

Supply voltage

8.0...30 VDC

Isolation voltage

Isolation voltage, test / working

1.5 kVAC / 50 VAC

Response time

Response time (programmable)

1...60 s

Voltage drop

8.0 VDC

Programming

Loop Link & HART

Signal / noise ratio

> 60 dB

Accuracy

Better than 0.05% of selected range

Signal dynamics, input

22 bit

Signal dynamics, output

16 bit

EMC immunity influence

< ±0.1% of span

Extended EMC immunity: NAMUR NE21, A criterion, burst

< ±1% of span

Input specifications

Common input specifications

Max. offset

50% of selected max. value

RTD input

RTD type

Pt50/100/200/500/1000; Ni50/100/120/1000

Cable resistance per wire

5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)

Sensor current

Nom. 0.2 mA

TC input

Thermocouple type

B, E, J, K, L, N, R, S, T, U, W3, W5, LR

Cold junction compensation (CJC)

Constant, internal or external via a Pt100 or Ni100 sensor

Voltage input

Measurement range

-800...+800 mV

Min. measurement range (span)

2.5 mV

Input resistance

10 MΩ

Output specifications

Current output

Signal range

4…20 mA

Min. signal range

16 mA

Load (@ current output)

≤ (Vsupply - 8) / 0.023 [Ω]

Sensor error indication

Programmable 3.5…23 mA

NAMUR NE43 Upscale/Downscale

23 mA / 3.5 mA

Common output specifications

Updating time

440 ms

HART protocol revisions

HART 7 and HART 5

I.S. / Ex marking

ATEX

II 1 G Ex ia IIC T6...T4 Ga, II 2 D Ex ia IIIC Db, I M1 Ex ia I Ma

IECEx

Ex ia IIC T6...T4 Ga, Ex ia IIIC Db, Ex ia I Ma

FM, US

Cl. I, Div. 1, Gp. A, B, C, D T4/T6; Cl. I Zone 0, AEx ia IIC T4/T6; Cl. 1, Div. 2, Gp. A, B, C, D, T4/T6

CSA

Cl. I, Div. 1, Gp. A, B, C, D Ex ia IIC, Ga

INMETRO

Ex ia IIC T6...T4 Ga, Ex ia IIIC Da, Ex ia I Ma

Observed authority requirements

EMC

2014/30/EU & UK SI 2016/1091

ATEX

2014/34/EU & UK SI 2016/1107

RoHS

2011/65/EU & UK SI 2012/3032

EAC

TR-CU 020/2011

EAC Ex

TR-CU 012/2011

Approvals

DNV Marine

TAA0000101

ATEX

DEKRA 20ATEX0108X

IECEx

DEK 20.0063X

FM

FM17US0013X

CSA

1125003

INMETRO

DEKRA 18.0002X

EAC Ex

RU C-DK.HA65.B.00355/19

SIL

Hardware assessed for use in SIL applications