Menu
Your Cart

3109

3109
3109
  • SKU: 3109
  • Label: 3109

Application

  • Isolation and conversion of standard DC signals.
  • Galvanic separation of analog current and voltage signals.
  • Elimination of ground loops and measurement of floating signals.
  • A competitive choice in terms of both price and technology for galvanic isolation of current and voltage signals to SCADA systems or PLC equipment.
  • Installation in ATEX Ex zone 2 / IECEx zone 2 / FM division 2.
  • Suitable for environments with high vibration stress, e.g. ships.

Technical characteristics

  • Easy configuration via DIP-switches.
  • The input is protected against overvoltage and polarity error.
  • Factory-calibrated measurement ranges.
  • Inputs and outputs are floating and galvanically separated.

Environmental Conditions

Operating temperature

-25°C to +70°C

Storage temperature

-40°C to +85°C

Calibration temperature

20...28°C

Relative humidity

< 95% RH (non-cond.)

Protection degree

IP20

Installation in

Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)

113 x 6.1 x 115 mm

Weight approx.

70 g

DIN rail type

DIN EN 60715/35 mm

Wire size

0.13...2.5 mm2 / AWG 26...12 stranded wire

Screw terminal torque

0.5 Nm

Vibration

IEC 60068-2-6

2...25 Hz

±1.6 mm

25...100 Hz

±4 g

Common specifications

Supply

Supply voltage

16.8...31.2 VDC

Max. required power

≤ 1.2 W

Max. power dissipation

0.60 W

Isolation voltage

Isolation voltage, test / working

2.5 kVAC / 300 VAC (reinforced)

Zone 2 / Div. 2

250 VAC

Response time

Response time (0...90%, 100...10%)

< 7 ms

Programming

DIP-switches

Signal / noise ratio

> 60 dB

Cut-off frequency (3 dB)

> 100 Hz

Signal dynamics, input

Analog signal chain

Signal dynamics, output

Analog signal chain

Accuracy

Better than 0.05% of selected range

Temperature coefficient

< ±0.01% of span / °C

EMC immunity influence

< ±0.5% of span

Extended EMC immunity: NAMUR NE21, A criterion, burst

< ±1% of span

Input specifications

Current input

Measurement range

0...23 mA

Programmable measurement ranges

0...20 and 4...20 mA

Input voltage drop

< 1.5 VDC

Voltage input

Measurement range

0...10.25 V 0...11.5 V / 0...5.75 V

Programmable measurement ranges

0/1...5 and 0/2...10 V

Input resistance

≥ 500 kΩ

2-wire transmitter supply

> 17 V / 20 mA

Output specifications

Current output

Signal range

0...23 mA

Programmable signal ranges

0 / 4...20 mA

Load (@ current output)

≤ 300 Ω

Load stability

≤ 0.002% of span / 100 Ω

Current limit

≤ 28 mA

Voltage output

Signal range

0...10 VDC

Programmable signal ranges

0/1...5 and 0/2...10 V

Load (@ voltage output)

≥ 10 kΩ

of span

= of the DIP-switch selected output range

I.S. / Ex marking

ATEX

II 3 G Ex ec IIC T4 Gc

IECEx

Ex ec IIC T4 Gc

FM, US

Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4

FM, CA

Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4

Observed authority requirements

EMC

2014/30/EU & UK SI 2016/1091

LVD

2014/35/EU & UK SI 2016/1101

ATEX

2014/34/EU & UK SI 2016/1107

RoHS

2011/65/EU & UK SI 2012/3032

EAC

TR-CU 020/2011

EAC Ex

TR-CU 012/2011

Approvals

ATEX

KEMA 10ATEX0147 X

IECEx

KEM 10.0068X

UKEX

DEKRA 21UKEX0055X

c FM us

FM17US0004X / FM17CA0003X

c UL us, UL 61010-1

E314307

CCC

2020322310003554

EAC Ex

RU C-DK.HA65.B.00355/19

DNV Marine

TAA00001RW